Delta Electronics VFD-VE Series manual 00-09, Energy Saving Gain Unit, Factory setting 100%, 00-10

Models: VFD-VE Series

1 291
Download 291 pages 55.35 Kb
Page 93
Image 93

Chapter 4 Parameters

 

00-09

Energy Saving Gain

Unit: 1

 

 

 

 

 

 

Control

FOCPG

 

Factory setting: 100%

 

mode

 

 

 

 

 

 

 

 

Settings

10~1000 %

 

 

 

 

 

 

When Pr.00-19 is set to1, this parameter can be used for energy saving. The setting should be decreased when the energy saving is not well. When the motor is vibrated, the setting should be increased.

 

00-10

Control Method

 

 

 

 

Control

VF

VFPG

SVC FOCPG TQRPG

Factory setting: 0

 

mode

 

 

 

 

 

 

 

 

 

Settings

0

V/f control

 

 

 

 

1

V/f + Encoder (VFPG)

 

 

 

 

2

Sensorless vector control (SVC)

 

 

 

 

3

FOC vector control + Encoder (FOCPG)

 

 

 

 

4

Torque control + Encoder (TQRPG)

 

 

 

 

 

 

 

 

This parameter determines the control method of the AC motor drive:

Setting 0: user can design V/f ratio by requirement and control multiple motors simultaneously.

Setting 1: User can use PG card with Encoder to do close-loop speed control.

Setting 2: To have optimal control characteristic by auto-tuning.

Setting 3: To increase torque and control speed precisely. (1:1000)

Setting 4: To increase accuracy for torque control.

00-11V/f Curve Selection

Control

VF

VFPG

 

Factory setting: 0

mode

 

 

 

 

 

 

 

Settings

0

V/f curve determined by group 01

 

 

1

1.5 power curve

 

 

2

Square curve

 

 

 

 

 

When it is set to 0, the V/f curve setting for the motor 1 is according to Pr.01-01~Pr.01-08 and Pr. 01-35~01-42 are for the motor 2.

When setting to 1 or 2, the settings of the 2nd voltage/frequency and the 3rd voltage/frequency are invalid.

4-44

Revision August 2008, 03VE, SW V2.04

Page 93
Image 93
Delta Electronics VFD-VE Series manual 00-09, Energy Saving Gain Unit, Factory setting 100%, 00-10, Control Method