Chapter 4 Parameters

3Pulse input (Pr.08-40)

4DFM-DCM pulse input (Pr.02-18)

When it is set to 1, 3 or 4, the current line speed will be saved into Pr.08-41 via analog and pulse command. When it is set to 2, it can change the setting of Pr.08-41 (current line speed) via communication.

When it is set to 3 or 4, pulse signal needs to be connected to PG2 of the PG card and then set the PG type by Pr.10-15.

When it is set to 3, it needs to use with Pr.08-40.

When it is set to 4, Pr.02-18 setting needs to be set to the DFM output value of previous driver as shown in the following before setting Pr.08-38.

tractor

Wind

the setting of P r,02-18 of motor 2 = the setti ng of Pr.02-18 of m otor 1

motor

Driv er 1

T P

DF M (02-18)

DFM

DCM

motor

Pr.10- 15 of motor 2 should be set to 3 or 4

Driv er 2

PG 2

A2 T P /A2

B2

/B2

DCM AB2

 

08-38

Max. Line Speed

 

Unit: 0.1

 

Control

VF

VFPG SVC

FOCPG TQRPG

Factory Setting: 1000.0

 

mode

 

 

 

 

 

 

 

 

Settings

0.0 to 3000.0 m/min

 

 

 

 

 

 

 

 

 

08-39

Min. Line Speed

 

Unit: 0.1

Revision August 2008, 03VE, SW V2.04

4-129