Chapter 4 Parameters

Group 9: Communication Parameters

There is a built-in RS-485 serial interface, marked RJ-11 near to the control terminals. The pins are defined below:

1: EV

2: GND 3: SG-

4: SG+

5: Reserved 6 1 6: Reserved

Each VFD-VE AC drive has a pre-assigned communication address specified by Pr.09-00. The RS485 master then controls each AC motor drive according to its communication address.

 

09-00

Communication Address

 

 

 

 

 

 

 

Control

VF

VFPG SVC FOCPG TQRPG

Factory Setting: 1

 

mode

 

 

 

 

 

 

 

Settings

1 to 254

 

If the AC motor drive is controlled by RS-485 serial communication, the communication

address for this drive must be set via this parameter. And the communication address for each

AC motor drive must be different and unique.

 

09-01

COM1 Transmission Speed

 

 

 

 

 

 

 

 

 

 

Control

VF

VFPG

SVC

FOCPG TQRPG

Factory Setting: 9.6

 

mode

 

 

 

 

 

 

 

 

 

 

Settings

4.8 to 115.2kbps

 

 

 

 

 

 

 

This parameter is used to set the transmission speed between the RS485 master (PLC, PC,

 

etc.) and AC motor drive.

 

 

 

 

 

 

 

09-02

COM1 Transmission Fault Treatment

 

 

 

 

 

 

 

 

 

 

Control

VF

VFPG

SVC

FOCPG TQRPG

Factory Setting: 3

 

mode

 

 

 

 

 

 

 

 

 

 

Settings

0

 

 

Warn and keep operating

 

 

 

 

1

 

Warn and RAMP to stop

 

 

 

 

2

 

Warn and COAST to stop

 

 

 

 

3

 

No warning and keep operating

 

 

 

 

 

 

 

 

 

This parameter is set to how to react if transmission errors occur.