Chapter 4 Parameters

The parameter is set by the output frequency, current and operation time of the drive for activating the I2t electronic thermal protection function. The function will be activated for the 150% * setting current for the setting of Pr.06-14/Pr.06-28.

Operation

time(min)

5

60Hz or more

4

50Hz

 

3

10Hz

2

5Hz

 

1

 

 

Load

0

20 40 60 80100120140160180200 factor (%)

06-15

Heat Sink Over-heat (OH) Warning

Unit: 0.1

Control

VF

VFPG

SVC FOCPG TQRPG

Factory Setting: 85.0

mode

 

 

 

 

 

 

Settings

 

0.0 to 110.0 oC

 

 

 

 

06-16

Stall Prevention Limit Level

Unit: 1

Control

VF

VFPG

SVC

Factory Setting: 50

mode

 

 

 

 

 

 

Settings

 

0 to 100% (refer to Pr.06-03, Pr.06-04)

 

 

 

 

 

 

When operation frequency is larger than Pr.01-01, Pr06-03=150%, Pr. 06-04=100% and Pr.

06-28=80%:

Stall Prevention Level during acceleration = 06-03x06-28=150x80%=120%.

Stall Prevention Level at constant speed= 06-03x06-28=100x80%=80%.

06-17Present Fault Record

 

06-18Second Most Recent Fault Record

 

 

 

 

06-19

Third Most Recent Fault Record

 

06-20

Fourth Recent Fault Record

 

06-21

Fifth Most Recent Fault Record

 

06-22

Sixth Most Recent Fault Record

 

 

Settings

0 to 65

Factory Setting: 0

 

 

 

 

Settings

Control Mode

VF VFPG SVC FOCPG TQRPG

4-100

Revision August 2008, 03VE, SW V2.04