Chapter 4 Parameters

 

Positive

 

 

torque

Forward motor mode

Reverse motor mode

 

06-12 current limit

 

06-12 current limit

 

 

 

External analog terminals

External analog terminals

Pr.03-00~02

Pr.03-00~02

7: positive torque limit

7: positive torque limit

10: positive/negative torque limit

10: positive/negative torque limit

9: regenerative torque limit

 

The level of torque limit will be

the min. value of following three values

1.torque limit of Pr.07-32 to Pr.07-35

2.Torque limit of external analog terminals (AVI, ACI and AUI)

3.Pr.06-12 current limit

 

 

Pr.07-35

Pr.07-32

 

 

 

 

Reverse regenerative

Forward motor

 

 

speed

 

torque limit

torque limit

 

speed

 

Quadrant II

Quadrant I

 

 

 

Quadrant III Quadrant IV

 

 

 

 

Pr.07-34

Pr.07-33

 

 

 

 

Reverse motor

Forward regenerative

 

 

 

 

torque limit

torque limit

 

 

 

External analog terminals

External analog terminals

 

 

Pr.03-00~03-02

Pr.03-00~03-02

 

 

8: negative torque limit

8: negative torque limit

 

 

10: positive/negative torque limit

10: positive/negative torque limit

 

06-12 current limit

Reverse motor modeNegative torque

06-12 current limit Forward motor mode

 

07-36

Emergency Stop (EF) & Forced Stop Selection

 

 

 

 

 

 

 

Factory Setting: 0

 

Control

VF

VFPG

SVC FOCPG TQRPG

 

mode

 

 

 

 

 

 

 

 

 

Settings

0

 

Coast stop

 

 

 

 

1

 

By deceleration Time 1

 

 

 

 

2

 

By deceleration Time 2

 

 

 

 

3

 

By deceleration Time 3

 

 

 

 

4

 

By deceleration Time 4

 

 

 

 

5

 

System Deceleration

 

 

 

 

6

 

Automatic Deceleration

 

 

 

 

 

 

 

 

When the multi-function input terminal is set to 10 or 18 and it is ON, the AC motor drive will be

operated by Pr.07-36.

4-118

Revision August 2008, 03VE, SW V2.04