Isolated Analog Programming Mode (ISOL)

Resistive-Controlled Current ISOL Setup

Activating ISOL Resistive-Controlled Current Setup

1.

Turn the 9-position mode control to the CAP position or press the

 

 

rotary Adjust/Enter control if the control knob is already at the CAP

 

 

position.

 

 

CAPr is displayed on the output voltage display.

 

2.

Turn rotary Adjust/Enter control to select R IS (voltage source

 

 

from isolated connector).

 

3.

Press the rotary Adjust/Enter control to commit the selected mode.

 

 

LE C is displayed on the output voltage display.

 

4.

Select the input source level using the rotary Adjust/Enter control.

 

5.

Once the desired level has been selected, press the rotary Adjust/

 

 

Enter control to commit the change.

 

 

The display will return to the normal display.

 

Deactivating ISOL Current Mode

4

To deactivate the ISOL current mode:

1.Turn the 9-position mode control to the CAP position or press the rotary Adjust/Enter control if the control knob is already at the CAP position.

2.CAPr is displayed on the output voltage display.

3.Turn the rotary Adjust/Enter control to select nonE.

4.Press the rotary Adjust/Enter control to commit the change. The display will return to the normal display.

M370078-01

4-31

Page 123
Image 123
Xantrex Technology XG 850 Resistive-Controlled Current Isol Setup, Activating Isol Resistive-Controlled Current Setup