Upgrading Modero Firmware

Selected Battery Base Firmware file

 

Description field for selected KIT file

 

Firmware download status

Device value and System number must match the values

listed in the Workspace window

FIG. 101 Send to NetLinx Device dialog (showing NXA-BASE/B firmware update via IP)

The firmware for the battery base can not be downloaded directly. Download of the KIT file to the BASE/B is done through the panel. The procedures for updating firmware to the base are nearly identical to those for updating panel firmware, except that the KIT file selected must be that of the BASE/B.

9.Click the Reboot Device checkbox. This causes the touch panel to reboot after the firmware update process is complete. The reboot of the panel can take up 30 seconds after the firmware process has finished.

10.Click Send to begin the transfer. The file transfer progress is indicated on the bottom-right of the dialog (FIG. 101).

11.Click Close on the Send to NetLinx dialog window (after the panel reboots) to return to the main program.

12.Right-click the associated System number and select Refresh System. This causes a refresh of all project systems, establishes a new connection to the Master, and populates the System list with devices on your particular system.

13.Press and hold the grey Front Setup Access button (below the LCD) for 3 seconds to access the Setup page.

14.Press the Battery Base button to open the Battery Base page and confirm that the version is no longer 0.00.

If the Base Version field displays 0.00, this means there was an error in the firmware download process. Re-install the base firmware and re-confirm that the new base version no longer reads 0.00.

VG-Series Modero Touch Panels

131

 

 

Page 141
Image 141
AMX NXD/NXT-1500VG, NXD/NXT-1700VG, NXD/NXT-1200VG manual VG-Series Modero Touch Panels 131