Advanced Energy®
Table
Command |
| Number of | Number of |
| Description | Host Data | Response |
|
| Bytes | Data Bytes |
|
|
|
|
8 | Specifies the output setpoint level for | 2 data bytes | 1 |
setpoint | whatever method of output regulation has |
| |
| been selected. Accepts a value of 0 to 8000 |
|
|
| W (for the 8 kW option) or 0 to 10000 W (for |
|
|
| the 10 kW option) when forward or load |
|
|
| power regulation is selected. Regular units |
|
|
| report in units of watts. HALO units report in |
|
|
| units of tenths of watts. |
|
|
|
|
|
|
9 | Specifies the external feedback value that | 3 data bytes |
|
max ext | corresponds to 10 V on the User port; |
| |
feedback | requires data bytes arranged as follows: |
| |
| • First/second byte = a |
|
|
| range of 500 to 5000. |
|
|
| • Third byte = the number of decimal |
|
|
| places (0 to 4) used to display the |
|
|
| external feedback signal on the operator |
|
|
| panel. |
|
|
|
|
|
|
11 | Specifies which target is active; accepts a | 1 data byte | 1 |
select | value of 1 to 4. (Readback command is 156.) |
| |
active |
|
|
|
target |
|
|
|
|
|
|
|
12 | Sets the life (in kWh) of the target you | 5 data bytes | 1 |
set target | specify. Requires five data bytes arranged as |
| |
life | follows: |
| |
| • First byte = the target number |
|
|
| • Second, third, fourth, fifth bytes = target |
|
|
| life in kWh |
|
|
| Note: A decimal is |
|
|
| send a value of 100. |
|
|
| (Readback command is 157.) |
|
|
|
|
|
|
14 | Sets the active control mode of the generator; | 1 data byte | 1 |
control | possible choices are: 2 = host, 4 = User port |
| |
transfer | (analog). |
|
|
|
|
|
|
15 | Specifies how long the generator can produce | 2 data bytes | 1 |
| output that is not equal to the programmed |
| |
setpoint | setpoint level. Accepts a value of 0 to 599 s. |
|
|
timer | (Readback command is 184.) |
|
|
|
|
|
|