Apex 1 to 5.5 kW Generator

Table 4-1.User Port 25-Pin APEX Standard Pin Descriptions (Continued)

Signal

Return

Name

Signal

Description

Pin

Pin

 

Type

 

 

 

 

 

 

22

9

OVERTEMP

Digital

When an internal

 

 

 

output

overtemperature shutdown

 

 

 

 

condition is detected, a low

 

 

 

 

(opto-coupler output) impedance

 

 

 

 

is created between this pin and

 

 

 

 

pin 9 (6 mA max).

 

 

 

 

See Wiring Diagram 4-9.

 

 

 

 

Note: This pin only detects a

 

 

 

 

overtemp shutdown

 

 

 

 

condition. The warning

 

 

 

 

indication described in the

 

 

 

 

Overtemp LED section is

 

 

 

 

not reported on this pin.

 

 

 

 

 

23

10

INTERLOCK LOOP

 

See Pin 10.

 

 

RETURN

 

 

 

 

 

 

 

24

11

DC BUS OK

Digital

When the interlocks are satisfied

 

 

 

output

and the AC input voltage is

 

 

 

 

within its specification, a low

 

 

 

 

(opto-coupler output) impedance

 

 

 

 

is created between this pin and

 

 

 

 

pin 11 (6mA max).

 

 

 

 

See Wiring Diagram 4-10.

 

 

 

 

 

25

 

CEX LOCK

Digital

See pin 12

 

 

RETURN

Output

 

 

 

 

 

 

WIRING DIAGRAMS FOR THE STANDARD 25-PIN USER PORT

The diagrams in this section provide wiring information to properly connect to the Apex standard 25-pin User port.

5708009-C

4-9

Page 55
Image 55
Apex Digital 5708009-C manual Wiring Diagrams for the Standard 25-PIN User Port, Return DC BUS OK