Bosch Appliances ICP-CC404 manual 0,14 Day Alarm Resetting

Models: ICP-CC404

1 98
Download 98 pages 40.39 Kb
Page 66
Image 66
0,14 Day Alarm Resetting

ICP-CC404 Installation Guide 16.0 Programmable Outputs

The output also operates during the Entry Guard Timer for STAY Mode time.

If a zone programmed for day alarm is activated when the system is disarmed, the output resets when the zone is resealed. You can turn Day Alarm on and off by pressing and holding [4]. Refer to Section 14.1 Day Alarm Information on page 53 for programming zones to operate for Day Alarm.

0,14 Day Alarm Resetting

This output operates when a zone programmed for Day Alarm is activated. The output resets when the Day Alarm zone is resealed. You can turn Day Alarm on and off by pressing and holding [4]. Refer to Section 14.1 Day Alarm Information on page 53 for programming zones to operate for Day Alarm.

0,15 Day Alarm Latching

This output operates when a zone programmed for Day Alarm is activated. The output resets by pressing [AWAY]. You can turn Day Alarm on and off by pressing and holding [4]. Refer to Section 14.1 Day Alarm Information on page 53 for programming zones to operate for Day Alarm.

1,0 Day Alarm Enabled

This output operates when Day Alarm is enabled. The output resets when Day Alarm is turned off. Refer to Section 14.1 Day Alarm Information on page 53 for programming zones to operate for Day Alarm.

You can turn Day Alarm on and off by pressing and holding [4]. Three beeps indicate that Day Alarm is turned on, two beeps indicate that Day Alarm is turned off. Refer to Section 6.3.7 Turning Day Alarm On and Off on page 38 for more information.

1,1 Telephone Line Fail

This output operates when the built-in telephone line fault module detects that the telephone line is disconnected longer than 40 sec. The output resets when the telephone line is restored continuously for longer than 40 sec. This output does not operate unless Option 1 in Location 176 is selected (refer to Section 11.11 Telephone Line Fault Options on page 49).

1,2 Kiss-Off Received

This output operates after the control panel successfully sends a message to the receiving party.

1,3 AUX Power Supply Fail

This output operates when either the 1 A codepad AUX power supply or the 1 A accessories AUX power supply fails. The output resets when the faulty AUX power supply is reset.

1,4

AC Fail

This output operates when the AC mains fails. The output resets when the AC mains is restored. This output operates regardless of whether Option 2 in Location 426 is selected (refer to Section 18.3 System Options 3 on page 74).

1,5 Low Battery

This output operates when a Dynamic Battery Test detects the battery failed or the battery voltage is below 11.2 VDC. The Dynamic Battery Test is performed every 4 hours after power is applied to the system and every time the system is armed.

This output resets only after a Dynamic Battery Test detects that the backup battery voltage is normal.

1,6 Horn Speaker Monitor Fail

If the Enable Monitoring of Horn Speaker (Option 2) in Location 424 is selected (refer to Section 18.1 System Options 1 on page 73), this output operates when the horn speaker is disconnected. The output resets when the horn speaker is reconnected.

1,7 Sensor Watch Alarm

This output operates when the Sensor Watch Count is reached. Refer to Section 14.3.4 Zone Options 1 on page 57 for more information on programming zones for sensor watch. Refer to Section 17.7 Sensor Watch Time on page 71 for setting the number of days before a zone registers as a faulty sensor watch zone.

1,8 Codepad Medical Alarm

This output operates when a user activates a Codepad Medical Alarm by pressing [7] and [9] at the same time on the remote codepad. This output resets when a valid User Code is entered at the remote codepad.

1,9 Codepad Fire Alarm

This output operates when a user activates a Codepad Medical Alarm by pressing [4] and [6] at the same time on the remote codepad. This output resets when a valid User Code is entered at the remote codepad.

1,10 Codepad Panic Alarm

This output operates when a user activates a Codepad Panic Alarm (audible or silent) by pressing either [1] and [3] or [STAY] and [AWAY] at the same time on the remote codepad. This output resets when a valid User Code is entered at the remote codepad.

1,11 Codepad Duress Alarm

This output operates when a user activates a Duress Alarm by adding a 9 to the end of the User Code used to disarm the system. This output resets the next time the system is armed.

66

Bosch Security Systems, Inc. 12/08 F01U089401-02

Page 66
Image 66
Bosch Appliances ICP-CC404 manual 0,14 Day Alarm Resetting