ICP-CC404 Installation Guide 17.0 System Event Timers

The Siren Sound Rate varies the frequency of the siren tone slowest (0) and to fastest (15). The Siren Sound Rate does not change the frequency of the fire alarm tone.

17.11 Auto Arming Pre-Alert Timer

Program the Auto Arming Pre-Alert Timer into Location 413 (increments of 5 min).

The default value for the Auto Arming Pre-Alert Timer is 1 (5 min).

This location sets the time period during which the control panel warns you it is automatically armed in AWAY Mode. The codepad beeps once every second until the Pre-Alert Timer expires: the system then automatically arms itself in AWAY Mode. If you want the system to automatically arm in STAY Mode 1, select Option 4 in Location 428 (refer to Section 18.5 Consumer Options 1 on page 75).

After the control panel automatically arms in AWAY Mode or STAY Mode 1, Exit Time starts. If a valid User Code is entered during the Pre-Alert Time, the Auto Arming Time programmed in Locations 414 to 417 (refer to Section 17.12 Auto Arming Time) is extended by 1 hour.

If you want a programmable output to operate during the Auto Arming Pre-Alert Time, use Output Event Type 0,5 Auto Arm Pre-Arming Alert Time (refer to page 65).

17.12 Auto Arming Time

Program the Auto Arming Time in Locations 414 to

417as described in Table 58.

The default value is midnight (0 0 0 0).

Table 58: Auto Arming Time Parameters

 

 

 

Location

Parameter

Default

414

Hour of day (tens digit)

0

415

Hour of day (units digit)

0

 

 

 

416

Minute of day (tens digit)

0

417

Minute of day (units digit)

0

 

 

 

These locations specify the time of the day that the system automatically arms itself in AWAY Mode. Set this time in 24-hour format (for example, program 10:30 PM as 2230). If you want the system to arm in STAY Mode 1, select Option 4 in Location 428 (refer to Section 18.5 Consumer Options 1 on page 75).

If forced arming is disabled for any zone, the automatic arming feature operates regardless of whether any zones are unsealed. Refer to Section

14.3.6Zone Options 2 on page 58 for more information on programming zones for forced arming.

User Code 16 is reported when this feature is used.

17.13 Auto Disarming Time

Program the Auto Disarming Time in Locations 418 to 421 as described in Table 59.

The default value is midnight (0 0 0 0).

Table 59: Auto Disarming Time Parameters

 

 

 

Location

Parameter

Default

418

Hour of day (tens digit)

0

419

Hour of day (units digit)

0

 

 

 

420

Minute of day (tens digit)

0

421

Minute of day (units digit)

0

 

 

 

These locations specify the time of day that the system automatically disarms itself. Set this time in 24-hour format (for example, program 10:30 PM as 2230).

User Code 16 is reported when this feature is used.

17.14 Kiss-Off Wait Time

Program the Kiss-Off Wait Time into Location 422 (increments of 500 millisec).

The default value for the Kiss-Off Wait Time is 3 (1500 ms).

This location sets the time that the control panel waits for acknowledgment before resending a report. This timer applies only to the 4 + 2 Express Format.

17.15 System Time

Program the System Time in Locations 901 to 904 as described in Table 60.

The default value is 0 0 0 0.

Table 60: System Time Parameters

 

 

 

Location

Parameter

Default

901

Hour of day (tens digit)

0

902

Hour of day (units digit)

0

903

Minute of day (tens digit)

0

904

Minute of day (units digit)

0

The ICP-CC404 Control Panel has a real-time

24-hour clock you must set during installation. Set this time in 24-hour HHMM format (for example, program 10:30 PM as 2230). You must reset the System Time every time power is removed from the system.

A Master Code holder can also set the System Date and Time (refer to Section 6.2.7 Setting the Date and Time on page 36).

17.16 System Date

Program the System Date in Locations 905 to 910 as described in Table 61.

The default value is 01 January, 2001 (0 1 0 1 0 1).

72

Bosch Security Systems, Inc. 12/08 F01U089401-02

Page 72
Image 72
Bosch Appliances ICP-CC404 manual Auto Arming Pre-Alert Timer, Auto Arming Time, Auto Disarming Time, Kiss-Off Wait Time