ICP-CC404 Installation Guide 4.0 System Operations
Zone Isolating Mode
| This indicator (the person) flashes once |
| every 3 sec when you attempt to isolate |
| zones or program zones to automatically |
Flashing | isolate for STAY Mode 2. |
|
For more information, refer to:
•Section 4.11 on page 21 to manually isolate zones.
•Section 6.1.4 on page 30 to use the Installer Code to set zones to automatically isolated in STAY Mode 2.
•Section 6.2.5 on page 35 to use the Master Code to set zones to automatically isolate in STAY Mode 2.
Fault Indicator
The fault indicator lights when the system detects a system fault (refer to Table 12 on page 17). Refer to Section
4.12Fault Analysis Mode on page 22 for more information on system faults.
Each time a new system fault is detected (the fault indicator flashes), the codepad beeps once per minute. Press [AWAY] to stop the beeping and acknowledge the fault.
Programming Mode
These two indicators flash when you enter Installer’s Programming Mode or use any Master Code function.
Flashing
OFF Indicator/Zone Sealed
The OFF indicator lights when the system is disarmed and flashes when a zone becomes unsealed when disarmed. The indicator stops flashing when all zones are sealed.
ON Indicator/Zone in Alarm
The ON indicator lights when the system is armed and flashes when an alarm occurs. The indicator resets after a valid User Code is entered.
Audible Indicators
The codepad provides a number of audible indications. Refer to Table 13 on page 17.
4.0 System Operations
There are two different methods to arm the system in AWAY Mode. You can always use the first method. You can use the other method only if Option 2 is enabled in Location 429 (refer to Section 18.6 Consumer Options 2 on page 75).
If you must isolate a zone(s) before arming the system in AWAY Mode, refer to Section 4.11 Isolating Zones on page 21.
Single button arming in AWAY Mode reports as User Code number 16.
To arm the system in AWAY Mode (method one): Enter your code and press [AWAY].
Two beeps sound, the AWAY indicator lights, and Exit Time starts.
To arm the system in AWAY Mode (method two):
Select Option 2 in Location 429 to enable single button arming in AWAY Mode (refer to Section 18.6 Consumer Options 2 on page 75).
1.Press and hold [AWAY].
2.When two beeps sound, release the button.
The AWAY indicator lights and Exit Time starts.
If a zone is not sealed at the end of Exit Time, the zone is automatically isolated and its indicator lights on the remote codepad. The zone becomes an active part of the system again after it is resealed. For example, if a window is open when Exit Time expires, the window is not an active part of the system until it is closed. Opening the window after Exit Time expires causes an alarm.
Forced Arming
Arming the system when a zone is not sealed is known as forced arming. Refer to Section 14.3.6 Zone Options 2 on page 58 to enable forced arming for each zone.
If the AWAY indicator does not light and a long beep sounds when you attempt to arm the system in AWAY Mode, forced arming is not permitted. If this is the case, you seal all zones or manually isolate them before you can arm the system.
4.2Disarming the System from AWAY Mode
This section explains the general operations of the system: arming and disarming the system in the three modes, isolating zones, initiating codepad alarms, and determining a fault.
4.1Arming the System in AWAY Mode
Arming the system in AWAY Mode is normally performed when you leave the premises and want all zones ready to detect an intrusion.
When you enter the premises after the system is armed in AWAY Mode, you must disarm the system from AWAY Mode to disable detection devices that activate the siren, strobe, and bell outputs.
If there was an alarm before disarming the system from AWAY Mode, a zone indicator flashes to indicate a previous alarm in that zone.
To disarm the system from AWAY Mode:
Enter your code and press [AWAY].
18 | Bosch Security Systems, Inc. 12/08 |