16.2Output Event Types

ICP-CC404 Installation Guide 16.0 Programmable Outputs

Example

3,0 Communications Failure

This event operates after the dialer makes all possible attempts to reach the base station receiver. It resets when the control panel receives the first kiss-off. This Output Event Type is not applicable to domestic reporting.

To redirect this Output Event Type to operate a codepad buzzer, program the Output Event Type as:

11,0 Communications Failure

The codepad buzzer now operates instead of the output that was programmed. Output 3 is no longer functional and cannot be used for any other Output Event Type.

16.2Output Event Types

There are approximately 60 Output Event Types. Two numbers designate each Output Event Type. Program these numbers into the appropriate locations for the output.

All reset times reference Polarities 1 and 8. Reset times vary depending on the selected polarity.

0,0 EDMSAT - Satellite Siren (Output 1 Only)

This output controls all functions of the SS914 Satellite Siren (EDMSAT). The Speaker Indication Beeps option does not function through the satellite siren for remote operations. No polarity is required for this Output Event Type.

0,1 System Armed

This output operates when the system is armed. The output resets when the system is disarmed.

0,2 System Disarmed

This output operates when the system is disarmed. The output resets when the system is armed.

0,3 Armed in STAY Mode

This output operates when the system is armed in STAY Mode 1 or STAY Mode 2. The output resets when the system is disarmed.

0,4 Armed in AWAY Mode

This output operates when the system is armed in AWAY Mode. The output resets when the system is disarmed.

0,5 Auto Arm Pre-Arming Alert Time

This output operates during the time period before the control panel is automatically armed in AWAY Mode or STAY Mode 1. The output resets when the control panel is automatically armed in AWAY Mode or STAY Mode 1. The Auto Arming Pre-Alert Time is programmed in Location 413 (refer to Section 17.11 on page 72 for more information).

0,6 Exit Warning with All Zones Sealed or Entry Warning

This output operates during Exit Time when the control panel is armed and all zones are sealed. The output resets when Exit Time expires.

This output operates again during Entry Time and resets when Entry Time expires or the system is disarmed.

This output also operates if a zone is activated when the system is armed in STAY Mode 1 or STAY Mode 2 and the Entry Guard Timer for STAY Mode is programmed in Locations 404 and 405 (refer to Section 17.5 on page 71).

0,7 Exit Warning

This output operates during Exit Time when the system is armed. The output resets when Exit Time expires.

0,8 Exit Warning Finished

This output operates after Exit Time expires when the system is armed. The output resets when the system is disarmed.

0,9 Kiss-Off after Exit Time

This output operates after the first successful transmission to the base station receiver when Exit Time expires. The output resets when the system is disarmed.

0,11 Entry Warning

This output operates when during Entry Timer 1, Entry Timer 2, or Entry Guard Timer for STAY Mode. The output resets when the Entry Time expires.

0,12 Entry Warning + Day Alarm Resetting

This output combines Entry Warning and Day Alarm Resetting so that either of these two events activates the output.

If the output is activated by Entry Timer 1, Entry Timer 2, or Entry Guard Timer for STAY Mode, the output resets when the Entry Time expires or the system is disarmed.

If a zone programmed for Day Alarm is activated when the system is disarmed, the output resets when the zone is resealed. You can turn Day Alarm on and off by pressing and holding [4]. Refer to Section 14.1 Day Alarm Information on page 53 for programming zones to operate for Day Alarm.

0,13 Exit Warning + Entry Warning + Day Alarm Resetting

This output operates when the system is armed, regardless of whether zones are sealed or unsealed, until Exit Time expires.

The output operates again during Entry Time and resets when Entry Time expires or the system is disarmed.

Bosch Security Systems, Inc. 12/08 F01U089401-02

65