15.11 Codepad Medical Report

ICP-CC404 Installation Guide 15.0 System Reporting Information

A Fire Alarm Report (Contact ID Event Code 110) is sent to the base station receiver when a user presses

[4]and [6] at the same time. A Fire Alarm is audible, but you can program the alarm as silent by selecting Option 2 in Location 425 (refer to Section 18.2 System Options 2 on page 73). A distinct fire sound is emitted through the horn speaker to indicate this type of alarm. The fire sound is different than the burglary sound.

Restore Reports are not sent for this event.

If Fire Reports are not required, program

Locations 339 and 340 as 0.

15.11 Codepad Medical Report

Program the Codepad Medical Report value in Location 341 (tens digit) and Location 342 (units digit).

The default values are 7 (tens) and 13 (units).

A Medical Report (Contact ID Event Code 100) is sent to the base station receiver when a user presses

[7]and [9] at the same time. A Medical Alarm is

audible, but you can program the alarm as silent by selecting Option 4 in Location 425 (refer to Section 18.2 System Options 2 on page 73).

Restore Reports are not sent for this event.

If Medical Reports are not required, program Locations 341 and 342 as 0.

15.12 Codepad Reporting Options

Use Location 343 to select whether Codepad Alarm Reports are sent to Receiver 1 (the default), Receiver 2, or both, Receiver 2 only when Receiver 1 fails, or there is no reporting at all. Table 47 lists the reporting options.

Table 48: Codepad Alarm Reporting Options

Option Description

0No Codepad Alarm Reports required

1

Receiver 1

2

Receiver 2

 

 

4Receiver 1 and Receiver 2

8Receiver 2 only when Receiver 1 fails

15.13System Status – AUX Power Supply Fail Report

Program the AUX Power Supply Fail Report value in Location 344 (tens digit) and Location 345 (units digit).

The default values are 10 (tens) and 3 (units).

A System Trouble Report (Contact ID Event Code

300)is sent when either the codepad AUX power supply or the accessories AUX power supply fails. The system reports the event approximately 10 sec after the AUX power supply fails.

15.14System Status – AUX Power Supply Fail Restore Report

Program the AUX Power Supply Fail Restore Report value in Location 346 (tens digit) and Location 347 (units digit).

The default values are 10 (tens) and 8 (units).

A System Trouble Restore Report (Contact ID Event Code 300) is sent when the failed codepad AUX power supply or the accessories AUX power supply is reset. The system reports the event approximately 10 sec after the AUX power supply is reset.

15.15 System Status – AC Fail Report

Program the AC Fail Report value in Location 348 (tens digit) and Location 349 (units digit).

The default values are 10 (tens) and 2 (units).

An AC Fail Report (Contact ID Event Code 301) is sent to the base station receiver when the AC mains supply is disconnected for 2 min. If you do not want an AC Fail Report to be sent until the AC mains supply is disconnected for 1 hour, select Option 1 in Location 426 (refer to Section 18.3 System Options 3 on page 74). If you want to ignore AC Fail, select Option 2 in Location 426.

If AC Fail Reports are not required, program Locations 348 and 349 as 0.

15.16System Status – AC Fail Restore Report

Program the AC Fail Restore Report value in Location 350 (tens digit) and Location 351 (units digit).

The default values are 10 (tens) and 7 (units).

An AC Fail Restore Report is sent when the AC mains supply is connected continuously for longer than 2 min.

If AC Fail Restore Reports are not required, program Locations 350 and 351 as 0.

15.17 System Status – Low Battery Report

Program the Low Battery Report value in Location 352 (tens digit) and Location 353 (units digit).

The default values are 10 (tens) and 1 (units).

62

Bosch Security Systems, Inc. 12/08 F01U089401-02

Page 62