Intel® NetStructureTMZT 7102 Chassis Management Module
Command Line Interface (CLI) Syntax and Arguments
Table 26. dataitem (-d) Keywords for Chassis Location
Data Item | Description | Get/ | Valid Set Values: | |
Set | ||||
|
|
| ||
|
|
|
| |
| Used to set or query the fan speed of all the fans in |
|
| |
| the system as a percentage of their full speed. Some |
|
| |
| fan trays may prevent the fan speed from going to |
|
| |
| zero. Querying the fan speed does not show actual |
| 100 (default) | |
| fanspeed, but reflects what the CMM fan speed output |
| ||
fanspeed | is set to as a percentage of the actual full fan speed. | Both | 80 | |
| See Section 17.0, “Fan Control and Monitoring” on |
| 0 | |
| page 91 for further information. |
| ||
|
|
| ||
| Note: In case of a temperature upper threshold |
|
| |
| violation, the fans will be automatically set by the |
|
| |
| CMM to run at full speed until the violation deasserts. |
|
| |
|
|
|
| |
| Used to set or query the value configured in the CMM |
| 2 (default) | |
healthyrampuptime | for the maximum amount of time the CMM will wait for | Both | through 60 | |
| the HEALTHY # hardware signal to be asserted by an |
| in seconds | |
| SBC. |
| ||
|
|
| ||
|
|
|
| |
| Used to set or query the location field in the chassis |
| Location String of | |
location | Both | up to 16 | ||
FRU. | ||||
|
| characters | ||
|
|
| ||
|
|
|
| |
| Used to set or query the value for the maximum |
| “ | |
|
| 0 | ||
maxpowerupattempts | number of tries the CMM will attempt to power up a | Both | ||
through | ||||
| board during the power sequencing loop. |
| ||
|
|
| 2000000000 | |
|
|
|
| |
psinhibit[1..8] | Used to inhibit the power supplies in the chassis. | Both | 1 - Enable | |
0- Inhibit | ||||
|
|
| ||
|
|
|
| |
| Queries chassis slot layout information. This will tell |
|
| |
slotinfo | the user what slots are system slots, peripheral slots, | Get | N/A | |
or busless slots. It will also show which slots are | ||||
|
|
| ||
| occupied by blades. |
|
| |
|
|
|
|
Table 27. dataitem (-d) Keywords for CMM Location (Sheet 1 of 2)
Data Item | Description | Get/ | Valid Set | |
Set | Values: | |||
|
| |||
|
|
|
| |
| Used to engage the Alarm Cutoff (ACO) or get its value. |
| 1 - Set cut off | |
| When engaged, the ACO silences active alarms and |
| ||
alarmcutoff | Both | 0 - Unset cut | ||
blinks the alarm LEDs on the CMM. This Dataitem is | ||||
|
| off | ||
| only valid when used with the CMM as the location. |
| ||
|
|
| ||
|
|
|
| |
| Used to set the Alarm Cutoff timeout value (in minutes) |
| Number of | |
| or get its value. This is the length of time the CMM waits |
| minutes: | |
alarmtimeout | before automatically canceling an engaged ACO (if the | Both | ||
user fails to cancel it manually). A value of 0 disables the | Value of 0 | |||
|
| |||
| timeout. This dataitem is only valid when used with the |
| disables the | |
| CMM as the location. |
| timeout. | |
|
|
|
| |
criticalled |
|
| 1 - Turn On | |
|
| LED | ||
minorled | Used to turn on or off the critical, major and minor LEDs. | Set | ||
0 - Turn Off | ||||
majorled |
|
| ||
|
| LED | ||
|
|
| ||
|
|
|
| |
Ethernet | Used to change to the eth0 direction to either the front | Both | front (default) | |
panel or the rear panel IO card. | rear | |||
|
| |||
|
|
|
|
60 | Technical Product Specification |