Intel® NetStructureTMZT 7102 Chassis Management Module
Health Event Strings
Executing a healthevents query through SNMP on a target with no active events returns different values than the CLI does. When a healthevents query is executed in SNMP on:
•A location target (i.e., in SNMP, the cmm target on the cmm location) that has no active events, the value returned is a zero length string.
•An individual sensor (i.e., the +3.3V sensor on the CMM) that has no active events, the value returned is a null value.
Note: Attempting to execute a healthevents query on the “FRU” target will return a “CLI Invalid Data Item Error.” string since “FRU” is not a sensor.
11.3.4Not Present or Non-IPMI Locations
Doing a healthevents query of a blade or powersupply, or a target on a blade or powersupply, that is not present or
“BPM Blade Not Present.” - if querying an empty blade slot.
“BPM Non IPMI Blade.” - if querying a blade that is present but doesn’t support IPMI.
“Power Supply Not Present.” - if querying an empty power supply slot or a power supply that doesn’t support IPMI.
11.4List of Possible Health Event Strings
Table 29 through Table 40 list possible event strings for sensors on the CMM, chassis, fan tray, and powersupply. Each event will log an entry in the SEL and generate an SNMP Trap, and can be retrieved through a healthevents query on a target or location. Locations and sensor names are listed as well.
The event severity is not displayed in the SEL entry or the SNMP trap. The severity of the event (Minor, Major, or Critical) is displayed in a healthevents query while the event is active. OK HealthEvents are displayed in healthevents queries for only a limited time when they are asserted.
For each event, the event code is listed in base 10 format for use with event scripting, which is documented in Section 18.0, “CMM Scripting” on page 93.
The table for
70 | Technical Product Specification |