Intel® NetStructureTMZT 7102 Chassis Management Module
Telco Alarm Sensors
22.3.1Sensor Names using SNMP
The telco alarm sensor names that will be shown via SNMP will be those that are defined at CMM startup. If a telco alarm sensor name has been changed after startup, the new name will not be reflected via SNMP until the CMM is restarted.
22.4Telco Alarm Sensors and Redundancy
In dual CMM systems, the telco alarm sensors are individual to each CMM in the system, and are not synchronized between the two CMMs. SEL entries from sensors on the active CMM will not be synched to the standby CMM.
If it is desired to monitor the same two inputs on both CMMs, the two inputs must be split into four and connected to the telco alarm connectors on both CMMs.
Telco alarm sensor names are synched between the two CMMs. Changing the name of the sensors on the active CMM will cause the same names to be assigned on the standby CMM.
122 | Technical Product Specification |