Intel® NetStructureTMZT 7102 Chassis Management Module

Fan Control and Monitoring

Note: Once the CMM automatically drives the fan speeds to 100 percent because of one of the above health events, it is still possible to set the fan speeds to 80 or 0 through the supported interfaces (CLI, etc). Once the automatic override of the fan speeds has been deactivated by resetting the fan speed to 80 or 0, the fans will remain at the newly set speed even after the condition that caused the automatic override has cleared.

17.3Querying Fan Tray Sensors

To query the fan trays and fan tray sensors, use fantrayN as the location (-l) of the cmmget command, where N is the number of the fan tray being queried. For example, to query the current value of FANTK1 on fantray1, issue the command:

cmmget -l fantray1 -t “FANTK1” -d current

92

Technical Product Specification

Page 92
Image 92
Intel ZT 7102 manual Querying Fan Tray Sensors