Intel® NetStructureTMZT 7102 Chassis Management Module
Hardware Specifications
2.3.2Chassis Sensor Connections
Chassis sensors are connected to the CMM via one
2.3.3Chassis FRU Device Connections
Chassis sensors are connected to the CMM via one
2.3.4Redundancy
The CMM supports redundant operation with automatic failover under hardware or software control. The following hardware interfaces exist for the support of redundancy and automatic failover:
•
•
•
The active CMM monitors its PRES_I# and HLY_I# inputs to determine if it has a healthy, standby CMM. The active CMM deasserts its HLY_O# output to trigger a failover to the standby CMM.
The
2.4Power Modules
Power supply sleds are connected to the CMM via two IPMBs. Each power supply sled connects to one IPMB. Multiple power supplies can share a single IPMB. The CMM also provides independent DEG#, FAIL#, and INH# signals as defined in PICMG* 2.11 for up to eight power supplies. The CMM will communicate with intelligent supplies via the IPMBs.
The CMM uses INH# rather than EN# to control the power supplies. The EN# pin is grounded on the backplane to signal to a power supply when it is fully seated in its connector.
2.5Fan Modules
Fan trays are connected to the CMM via one
Technical Product Specification | 19 |