Schneider Electric IP67 manual 119

Models: IP67

1 198
Download 198 pages 30.62 Kb
Page 119
Image 119

Software Tools

Step

Action

 

 

 

 

 

 

 

 

 

 

 

2

 

Complete the fields:

 

 

 

 

 

 

 

 

 

 

 

 

 

Request: "Write SDO" or "Read SDO"

 

 

Node: address of the device on the CANopen network

 

 

Index: index of the object to read or write

 

 

Sub-index: sub-index of the object to read or write

 

 

￿Value: entry area for the data to be sent, for write only

 

 

Click "Send".

 

 

 

 

 

 

 

 

 

 

 

 

Here is an example of how to configure the Inhibit Time to 1000 ms:

 

￿

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Enter CANopen Request

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Request:

 

Write SDO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Node:

 

1

 

 

 

 

 

 

 

 

 

 

￿

 

 

 

 

 

 

 

 

 

 

 

 

 

Index:

16#

1800

 

 

 

 

 

 

 

 

 

 

Sub-index:

16#

3

 

 

 

 

 

 

 

 

 

 

 

Value:

16#

10 27 00 00

 

 

 

 

 

 

 

(120 bytes max.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Send

 

 

 

 

 

 

Cancel

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The value "10 27 00 00" corresponds to the number 2710 in hexadecimals, which is 1000 ms (see Inhibit Time and Event Timer, p. 60).

3After a "Read SDO", read the value given in the "Received response" area in the bottom-right of the debug screen:

 

 

 

Slave information

 

 

 

 

Node 10: Status=08h, AddInfo=0001h,

Total

 

 

 

 

No. of slaves No. Input %MW No. Output %MWsRequest to be sent

Received response

0011

83

113

Enter

 

 

 

 

request

 

1606218 02 08/2006

119

Page 119
Image 119
Schneider Electric IP67 manual 119