The Object Dictionary

Object 1017H: Producer Heartbeat Time

Description

This object is used to configure the time interval in ms within which the module must

 

produce the Hearbeat message.

 

The default monitoring method of the splitter is "Node Guarding". If a non-zero value

 

is written in this object the Heartbeat mechanism is used.

Object

 

The characteristics of this object are outlined in the following table:

Characteristics

Sub-index

Description

Data type

Default value

Access

PDO

Backed up

 

 

 

 

 

Mapping

 

 

 

 

 

 

 

 

0

-

UNSIGNED16

0H

rw

no

yes

 

 

 

 

 

 

 

If the Heartbeat error monitoring protocol is selected, the splitter box sends a Heartbeat message periodically, depending on the "Producer Heartbeat Time" parameter. The products responsible for monitoring this message (Heartbeat Consumer) generate a Heartbeat event if the message is not received within the configured time (Consumer Heartbeat Time) in their object 1016H. "Node- Guarding" and "Life-Guarding" Monitoring Protocols, p. 62