The Object Dictionary

Object 1006H: Communication Cycle Period

Description

This object describes the time interval between two SYNC signals in microseconds.

 

This interval must be at least 10 ms with a minimum increment of 1ms. The entry

 

must be a double word.

 

If a value between 10,000 and 10,000,000 is entered, the splitter must receive a

 

SYNC signal within this time interval. If not, it switches to "Pre-Operational" status.

 

Maximum tolerance is 1% of the configured value. Monitoring of elapsed times starts

 

when the first SYNC signal is received.

Object

 

The characteristics of this object are outlined in the following table:

Characteristics

Sub-index

Description

Data type

Default

Access

PDO

Backed up

 

 

 

value

 

Mapping

 

 

 

 

 

 

 

 

0

-

UNSIGNED32

0

ro

no

no

 

 

 

 

 

 

 

Note: It is not advisable to use this object as it can create communication errors in slow speed.