The Object Dictionary

Object 1011H: Restore Default Parameters

Description

 

This object is used to restore the FTB splitter box's "factory" settings.

Characteristics

 

 

 

 

 

 

The characteristics of this object are outlined in the following table:

 

 

 

 

 

 

 

 

Sub-index

Description

Data type

Default

Acce

PDO Mapping

Backed up

 

 

 

 

value

ss

 

 

 

 

 

 

 

 

 

0

Sub-index number

UNSIGNED8

4

ro

no

no

 

 

 

 

 

 

 

1

Restore all default

UNSIGNED32

-

rw

no

no

 

parameters.

 

 

 

 

 

 

 

 

 

 

 

 

2

Restore default

UNSIGNED32

-

rw

no

no

 

communication

 

 

 

 

 

 

parameters (1000H–

 

 

 

 

 

 

1FFFH).

 

 

 

 

 

 

 

 

 

 

 

 

3

Restore default

UNSIGNED32

-

rw

no

no

 

standardized application

 

 

 

 

 

 

parameters (6000H–

 

 

 

 

 

 

9FFFH).

 

 

 

 

 

 

 

 

 

 

 

 

4

Restore default

UNSIGNED32

-

rw

no

no

 

manufacturer-specific

 

 

 

 

 

 

application parameters

 

 

 

 

 

 

(2000H–5FFFH).

 

 

 

 

 

 

 

 

 

 

 

 

 

Operation

 

 

 

 

 

 

 

 

To restore the parameters, the "load" ASCII character string (64616F6CH) must be

written to the corresponding sub-index:

 

Most significant word

Least significant

 

 

 

word

 

 

 

 

 

 

ISO 8859

d

a

o

l

(ASCII)

 

 

 

 

signature

 

 

 

 

 

 

 

 

 

Hex value

64H

61H

6FH

6CH

 

 

 

 

 

The read result of a sub-index is always 0000 0001H.