The Object Dictionary

Object 6306H:Fallback Mode 16 Bits

Description

This object is used to define discrete output status value in the event of an error. This

 

value is either that defined by the 6307H object, or the most recent value received

 

before error occurrence (maintain mode).

 

 

 

 

 

Value

State of value

 

 

 

 

 

 

0

Maintain

 

 

 

 

 

 

1

Fallback (see object 6307H)

 

 

 

 

 

 

 

 

 

Characteristics

The characteristics of this object are outlined in the following table:

 

 

 

 

 

 

 

 

Sub-

Description

Data type

Default value

Access

PDO Mapping

Backed up

index

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

Sub-index number

UNSIGNED8

1

ro

no

yes

 

 

 

 

 

 

 

1

Fallback mode

UNSIGNED16

FFFFH

rw

no

yes

 

 

 

 

 

 

 

 

Note: When the value of object 6306H is FFFFH, all discrete outputs take the fallback value defined by object 6307H in the event of a fault.

1606218 02 08/2006

183

Page 183
Image 183
Schneider Electric IP67 Object 6306HFallback Mode 16 Bits, Before error occurrence maintain mode, Value State of value