Installation

 

 

Control of

The outputs of the devices described in this manual are equipped with an integrated

Inductive Loads

protective system against the high noise voltages that may be generated by

 

inductive loads.

 

Integrated protective system against the high noise voltages generated by inductive

 

loads

Varistor

Inductive load

e.g. electromagnetic valve

The varistor rapidly discharges the energy accumulated in the magnetic field of the inductive load.

The high voltages arising from the disconnection of inductive loads create large fields in the wires that may cause disturbances in nearby circuits or devices. It is advisable to provide an anti-interference device at the load level. In this way, the voltage peak generated by the inductive load is short-circuited directly at the point at which it occurs.