The Object Dictionary

 

 

 

 

 

 

 

 

Object 1002H: Manufacturer Status Register

 

 

 

 

Description

 

 

 

 

 

 

 

 

 

The diagnostics data is saved in this 32-bit field.

 

 

 

 

The least significant word (LSW) contains the error code.

 

 

Characteristics

 

 

 

 

 

 

 

The characteristics of this object are outlined in the following table:

 

 

 

 

 

 

 

 

Sub-index

Description

Data type

Default value

Acces

PDO

Backed up

 

 

 

 

 

 

s

Mapping

 

 

 

 

 

 

 

 

 

 

 

0

-

 

UNSIGNED32

80H (see note)

ro

no

no

 

 

 

 

 

 

 

 

 

 

Assignment of Bits

Note: At initial start-up, channels 10 to 17 are configured as "diagnostics inputs" by default.

Note: Bit Values:

0: no fault

￿1: fault

The following table indicates the assignment of the 32 bit set:

Bit

Meaning

Notes

 

 

 

 

 

0

Sensor under voltage < 18V

 

 

 

 

 

 

1

No voltage in sensor < 12V

 

 

 

 

 

 

2

Actuator under voltage < 18V

 

 

 

 

 

 

3

No voltage in actuator < 12V

 

 

 

 

 

 

4

Sensor power supply short-circuit in M12

 

 

 

 

 

 

5

Actuator short-circuit

Only where output is set-up

 

 

 

 

 

6

Actuator warning

Only where output is set-up

 

 

 

 

 

7

Detection of wire cut

 

 

 

 

 

 

8 to 31

Reserved

 

 

 

 

 

 

 

 

 

 

 

 

1606218 02 08/2006

137