CANopen Network Interface

List of Saved Parameters

Communication

The objects that are saved or reused on start-up are as follows:

Profile Objects

1005H : COB-ID SYNC Message

 

1006H

: Communication Cycle Period

 

100CH : Guard Time

 

100DH : Life Time Factor

 

1014H

: COB-ID Emergency Message (EMCY)

 

1016H

: Consumer Heartbeat Time

 

1017H

: Producer Heartbeat Time

 

1400H...1405H : Receive PDO Communication Parameters

 

1600H...1605H : Receive PDO Mapping Parameters

 

1800H...1805H : Transmit PDO Communication Parameters

 

1A00H...1A05H : Transmit PDO Mapping Parameters

Discrete I/O

 

 

 

The discrete I/Os configuration objects are as follows:

Configuration

2000H : Input / Diag Parameter

Objects

2001H : Input / Output Parameter

 

6102H

: Polarity Inputs

 

6103H

: Filter Constant Input 16 Bits

 

6200H

: Write Outputs 8 Bits

 

6300H

: Write Outputs 16 Bits

 

6302H

: Polarity Outputs 16 Bits

 

6306H

: Fallback Mode 16 Bits

 

6307H

: Fallback Value 16 Bits

 

￿6308H : Filter Mask Outputs 16 Bits

 

 

 

 

 

 

 

 

 

DANGER

 

 

 

 

 

 

 

 

 

 

RISK OF UNINTENDED EQUIPMENT OPERATION

 

Check the contents of objects 6200H and 6300H before switching the product in

 

"Operational" state. Output write objects 6200H and 6300H are saved. Following

 

power up, the switch to "Operational" state will apply to the saved output values.

 

Failure to follow this instruction will result in death or serious injury.

 

 

 

 

 

 

 

 

 

 

70

1606218 02 08/2006

Page 70
Image 70
Schneider Electric IP67 manual List of Saved Parameters, Profile Objects, Discrete I/O, Configuration