The Object Dictionary

Object 1016H: Consumer Heartbeat Time

Description

 

This object is used to monitor the communication of another product on the network.

 

 

 

It is particularly used to monitor the master. The value of this object defines the time

 

 

 

interval within which the monitored product must send a Heartbeat message.

 

 

 

The splitter box is designed in such a way that it can only monitor one product at a

 

 

 

time.

 

 

 

 

 

 

 

 

 

 

The value of this object must be greater than the value of object 1017H of the

 

 

 

monitored product.

 

 

 

 

 

 

 

 

 

The time must be a multiple of 1 ms.

 

 

 

 

 

Object

 

 

 

 

 

 

 

 

 

 

 

 

The characteristics of this object are outlined in the following table:

 

 

Characteristics

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sub-index

Description

Data type

 

Default

Access

PDO

Backed up

 

 

 

 

 

 

 

value

 

Mapping

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

Sub-index

UNSIGNED8

 

1

ro

no

yes

 

 

number

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

Consumer

UNSIGNED32

 

0

rw

no

yes

 

 

heartbeat time

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Content of

 

 

 

 

 

 

 

 

 

 

 

 

The content of sub-index 1 is as follows:

 

 

 

 

 

Variable

 

 

 

 

 

 

 

 

 

 

 

 

Bit

 

31 to 24

23 to 16

 

 

15 to 0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Value

 

0H (Reserved)

Address of the monitored splitter

Monitoring time in ms

 

 

 

 

 

 

box

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

If the value of the sub-index is 0, no splitter box is monitored.

 

 

"Node-Guarding" and "Life-Guarding" Monitoring Protocols, p. 62