Schneider Electric IP67 manual Object 1800H 1st Transmit PDO Communication Parameter

Models: IP67

1 198
Download 198 pages 30.62 Kb
Page 161
Image 161

The Object Dictionary

Object 1800H: 1st Transmit PDO Communication Parameter

Description

 

This object contains the PDO transmit identifier.

 

 

 

Characteristics

 

 

 

 

 

 

The characteristics of this object are outlined in the following table:

 

 

 

 

 

 

 

 

Sub-index

Description

Data type

Default value

Access

PDO

Backed up

 

 

 

 

 

 

Mapping

 

 

 

 

 

 

 

 

0

Sub-index

UNSIGNED8

5H

ro

no

yes

 

number

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

COB-ID

 

UNSIGNED32

0000 0180H + Node ID

rw

no

yes

 

 

 

 

 

 

 

2

Transmission

UNSIGNED8

FFH (255 dec.)

rw

no

yes

 

mode

 

 

 

 

 

 

 

 

 

 

 

 

 

3

Inhibit Time

UNSIGNED16

0

rw

no

yes

 

 

 

 

 

 

 

4

Not available

 

 

 

 

 

 

 

 

 

 

 

 

5

Event Timer

UNSIGNED16

0

rw

no

yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1606218 02 08/2006

161

Page 161
Image 161
Schneider Electric IP67 manual Object 1800H 1st Transmit PDO Communication Parameter