Diagnostics

Error Codes

The table below lists the error codes and their meanings:

 

(EMCY bytes

 

 

 

 

Error

Diagnostics

Description

 

0&1)

 

code

 

 

 

 

 

 

 

 

 

 

 

 

 

0000H

ERROR_RESET_OR_NO_ERROR

Clearing of one, or all, errors

 

 

 

 

 

 

 

1000H

GENERIC_ERROR

Internal communication error

 

 

 

 

 

 

 

2100H

CURRENT_DEVICE_INPUT_SIDE

Detector power supply short-circuit

 

 

 

 

(M12 connector)

 

 

 

 

 

 

 

2320H

SHORT_CIRCUIT_AT_OUTPUTS

Output short-circuit

 

 

 

 

 

 

 

3100H

MAINS_VOLTAGE

Splitter power supply voltage < 18V

 

 

 

 

 

 

 

3120H

INPUT_VOLTAGE_TOO_LOW

Sensor power supply voltage < 18V

 

 

 

 

 

 

 

3310H

OUTPUT_VOLTAGE_TO_HIGH

Actuator power supply voltage > 30V

 

 

 

 

 

 

 

3320H

OUTPUT_VOLTAGE_TO_LOW

Actuator power supply voltage < 18V

 

 

 

 

 

 

 

6101H

SOFTWARE_RX_QUEUE_OVERRUN

The receive buffer has exceeded its

 

 

 

 

internal memory capacity

 

 

 

 

 

 

 

6102H

SOFTWARE_TX_QUEUE_OVERRUN

The transmit buffer has exceeded its

 

 

 

 

internal memory capacity

 

 

 

 

 

 

 

8100H

COMMUNICATION

Synchronization, transmit/receive error

 

 

 

 

counter > 96

 

 

 

 

 

 

 

8120H

CAN_IN_ERROR_PASSIVE_MODE

CAN controller interrupted

 

 

 

 

 

 

 

8130H

LIFE_GUARD_ERROR

Node-Guarding error

 

 

 

 

 

 

 

8140H

BUS_OFF

The transmit error counter has

 

 

 

 

exceeded its capacity

 

 

 

 

 

 

 

9000H

EXTERNAL_ERROR

Detection of wire cut on sensor

 

 

 

 

 

 

 

F000H

ADDITIONAL_FUNCTION

Actuator voltage < 12VDC

 

 

 

 

 

 

 

 

 

 

 