The Object Dictionary

Object 2000H: Input / Diag Parameter

Description

For channels 10 to 17 (connector pin 2) this object is used to select the "input" or

 

"diagnostics input" function.

 

Channels 10 to 17 are configured as "diagnostics input" by default.

 

The diagnostics inputs enable the use of sensors integrating a wire cut detection

 

function.

 

 

 

 

 

 

 

Note: For configurable channels, this object's status is taken into account only if

 

the input channel is configured by the 2001H object.

 

 

 

 

 

The following table shows the configuration of channels 10 to 17 according to their

 

sub-index bit value:

 

 

 

 

 

Status

Description

 

 

 

 

 

 

0

Discrete input

 

 

 

 

 

 

1

Diagnostics input

 

 

 

 

 

 

 

 

 

Characteristics

The characteristics of this object are outlined in the following table:

 

 

 

 

 

 

 

 

Sub-

Description

Data type

Default value

Access

PDO Mapping

Backed up

index

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

Sub-index number

UNSIGNED8

1

ro

no

yes

 

 

 

 

 

 

 

1

Input parameter/

UNSIGNED8

FFH

rw

no

yes

 

diagnostics input

 

 

 

 

 

 

 

 

 

 

 

 

 

Note: Channels 10 to 17 are configured as "diagnostics inputs" by default.

172

1606218 02 08/2006

Page 172
Image 172
Schneider Electric IP67 manual Object 2000H Input / Diag Parameter, Diagnostics input function, Sub-index bit value