Splitter Box Characteristics and Wiring
Connecting the Actuators and Sensors
Description
Characteristics of the Connections
The actuators and sensors are connected to the FTB splitter box using
The maximum admissible load for the FTB splitter boxes is limited to:
1.6 A per output (actuator current),
200 mA for both inputs (sensor current).
WARNING
RISK OF EQUIPMENT DAMAGE AND NON-COMPLIANCE WITH IP67
Unused M12 connectors must not be left unprotected. If an M12 connector is not correctly connected to the end of another connector or standard cable, fit a sealing plug in order to ensure that the product is IP67 standard compliant. To ensure the IP67 protection index, check that the cover is screwed onto the base splitter box and that all connectors are fitted with cables or sealing plugs.
Failure to follow this instruction can result in death, serious injury, or equipment damage.
Assignment of The following diagram shows the front view of a
M12 Connector convention for numbering the pins:
Pins
Pin | Assignment |
|
|
|
|
1 | +24 VDC |
|
|
|
|
2 | Channel 10 to 17: diagnostics input or functional input or output |
|
|
|
|
3 | 0 VDC |
|
|
|
|
4 | Channel 00 to 07: functional input or output |
|
|
|
|
5 | Ground |
|
|
|
|
|
|
|
30 | 1606218 02 08/2006 |