Status Register The object 1001H (Error Register) is a byte used by the device to display internal

(EMCY Byte 2) errors when an error is detected:

Bit

Description

Comments

 

 

 

 

0

Generic error

See Object 1003H

 

 

 

 

1

Current fault (overload or short-circuit)

See Object 1003H

 

 

 

 

2

Voltage fault

See Object 1003H

 

 

 

 

3

Temperature

Unchecked

 

 

 

 

4

Communication error

See Object 1003H

 

 

 

 

5

Reserved

Unchecked

 

 

 

 

6

Reserved

Unchecked

 

 

 

 

7

Specific to the manufacturer

Detection of wire cut on sensor

 

 

 

 

 

 

 

 

Channel

Data returned in bytes 5 and 6 is the image of channels with the error defined by

Diagnostics

EMCY byte 7 (manufacturer status register):

 

(EMCY Bytes 5-6-

 

 

 

 

Byte

6 (channels 0 to 7)

5 (channels 10 to

7

7)

 

 

17)

 

 

 

 

 

 

 

 

 

 

 

Contents

Faulty channels

Faulty channels

Types of faults

 

 

 

 

 

The following table indicates the assignment of all EMCY byte 7 bits:

Bit

Description

Comments

 

 

 

0

Sensor under voltage

< 18V

 

 

 

1

No voltage in sensor

< 12V

 

 

 

2

Actuator under voltage

< 18V

 

 

 

3

No voltage in actuator

< 12V

 

 

 

4

Sensor power supply short-circuit

< 12V

 

 

 

5

Actuator short-circuit

only where output is set-up

 

 

 

6

Actuator overload

only where output is set-up

 

 

 

7

Detection of wire cut on sensor

-

 

 

 

 

 

 

1606218 02 08/2006

129