The Object Dictionary

Object 100DH: Life Time Factor

Description

 

This object contains the "Life-Time-Factor" parameter. It is used to calculate the

 

 

"Life-Time".

 

 

 

 

 

Object

 

 

 

 

 

 

 

 

 

The characteristics of this object are outlined in the table below: "Node-Guarding"

Characteristics

and "Life-Guarding" Monitoring Protocols, p. 62

 

 

 

 

 

 

 

 

 

 

Sub-index

Description

Data type

Default

Access

PDO

Backed up

 

 

 

 

 

value

 

Mapping

 

 

 

 

 

 

 

 

 

 

 

0

-

 

UNSIGNED8

0

rw

no

yes

 

 

 

 

 

 

 

 

 

 

Reliable

 

 

 

 

 

 

 

 

 

To enable reliable and secure operation, the user must enter a "Life-Time-Factor"

Operation

 

with a minimum value of 2.

 

 

 

 

When the value 1 is used, should a delay occur due to the processing of high priority messages or internal processing on the "Node-Guarding" master, the splitter switches back to the "Pre-Operational" default state without generating any errors.

WARNING

RISK OF UNINTENDED DEVICE OPERATION

Set the "Life-Time-Factor" to a minimum value of 2 to prevent any inadvertent change of state to "Pre-Operational" state. Depending on the I/O configuration, an inadvertent change of state may result in unintended device operation.

Failure to follow this instruction can result in death, serious injury, or equipment damage.

1606218 02 08/2006