CANopen Network Interface

Line Terminator To minimize the voltage drop in the connection, it is advisable to use a higher line

Resistance terminator resistance for high length cables than that specified by the standard ISO11898-2. When configuring the system, the connector resistances must also be taken into consideration. For each connector, 5 mΩ to 20 mΩ must be added to the terminator resistance.

WARNING

RISK OF UNINTENDED EQUIPMENT OPERATION

The potential difference at the CAN_GND connections of all the CANopen bus items must not be greater than 2 VDC. The connectors have a standard DC of

5mΩ to 20 mΩ. It is important to connect a 120 Ω line terminator between CAN_H and CAN_L at the line end (see Physical Layer, p. 49).

Failure to follow this instruction can result in death, serious injury, or equipment damage.

What types of Pre-assembled cables make installing the system considerably easier. Cabling

cables can be errors are avoided and implementation is achieved more rapidly. Schneider Electric

used?offers a full range of products such as field bus links, power supply cables and cables for detectors, together with accessories such as line terminators. Connectors and cables for assembly are also available.