Splitter Box Characteristics and Wiring

Pin Assignment The following diagram shows a front view of the PWR IN and PWR OUT connectors:

Recommen- dations for the Power Supply to the Sensors, Actuators and Splitter Boxes

Emergency Stop

Pin

Assignment

10 VDC

20 VDC

3Ground

4Splitter box sensor and power supply

5Actuator power supply

We recommend the use of 2 independent power supplies so as to separate the power supply to the splitter boxes / sensors from the power supply to the actuators.

This configuration provides maximum protection against any disturbance on the outputs (short circuits).

Separating the splitter box/sensor (pin 4) power supplies means that the emergency stop can be connected to the actuator power supply (pin 5 of the 7/8" connector).

WARNING

RISK OF UNINTENDED EQUIPMENT OPERATION

Do not connect pin 4 of the power supply connector to the emergency stop circuit of the system. Interrupting the power supply to this pin, will deactivate the I/O channels of the splitter box, which can result in an unintended equipment operation.

Failure to follow this instruction can result in death, serious injury, or equipment damage.

1606218 02 08/2006

33

Page 33
Image 33