Installing the External PDU into the Rack
WARNING: Whenever you need to lift the system, get others to assist you. To avoid injury, do not attempt to lift the system by yourself.
NOTE: The PDU device illustrations are provided as reference only. See PDU device documentation for more information about the PDU device.
NOTE: The PDU mounting brackets are marked L and R. The rail marked "L" attaches to the left of the PDU device and the rail marked "R" attaches to the right of the PDU device.
WARNING: Do not connect or disconnect power cables to the PDU device while the PDU is energized.
WARNING: Turn off the PDU breaker switches to avoid potentially serious or fatal electric shock.
1Power down the PDU.
a Turn off the PDU breaker switches by moving the A, B, and C breaker switches to the "OFF" position.
Figure 4-7. Turning off the PDU Breaker Switches
1 |
|
|
O F F | O F F | O F F |
2
Rack Mount Configuration