Checking PDU Indicators

The PMC power/status and identification indicators lights to indicate an error condition.

Power/status indicator blinks amber (about 1 Hz) to indicate an error condition.

Identification indicator blinks blue (about 1 Hz).

Resetting the PDU Network Connection

By default, the PMC is configured to automatically obtain an IP address via DHCP server.

1Do three short presses of the reset button within 5 seconds to change the DHCP IP address on the PMC over to a static IP address.

After the PMC resets, all network and configuration settings restore back to their default values. The PMC is configured with the following default network settings:

IP address: 192.168.0.120

Subnet mask: 255.255.255.0

Gateway: 192.168.0.1

The power/status indicator on the front of the PMC board displays the following behaviors:

Blinking amber (500 ms off/5 s on) — Restarts the PMC firmware and reset to factory default is completed.

Blinking amber (250 ms off/5 s on) — Restores the default network settings to their default values.

2Do three short presses of the reset button within 5 seconds again to switch static IP back to reset to default (DHCP).