8.7.4I/O Controller Module

The following flowchart provides troubleshooting procedures for the I/O controller module.

4A

I/O controller module problem (FC)

SFP Link LED

 

 

Replace

 

Yes

SFP with known

Replace

Try a

Replace I/O

known good

amber?

good SFP.

 

the cable.

HBA.

controller module.

 

 

 

No

 

 

 

Resolved?

No

 

 

Yes

 

 

 

 

 

 

End

 

 

 

Check event

RAID controller

Yes

messages in

status amber?

2

firmware or software

 

 

 

 

messages.

 

 

 

No

Resolved?

Yes

End

Replace I/O controller

module.

No

Resolved?

Yes

End

Power off.

Place known good I/O controller module in slot.

Power on.

Yes

No

No

Battery LED

Yes

solid amber?

Message

Resolved?

 

"Controller has

 

failed" is

 

displayed?

 

 

Yes

End

No

Pull battery

 

 

 

 

 

 

 

module and

 

 

 

 

 

Replace battery.

reseat it.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No

 

 

 

 

 

 

 

 

 

 

 

Resolved?

Yes

End

No

Replace chassis.

Notes

Fibre Channel arrays use small form-factor (SFP) connectors to attach the array to hosts and expansion units. Each Fibre Channel I/O controller module has six SFP ports. These ports are labeled FC0 through FC5.

No

Resolved?

Yes

 

 

.

 

Yes

 

End

End

End

Replace battery module if it is close to the 2 year life limit.

Prior to replacing a chassis, try the following: --Reseat the FRU that is not operating correctly. --Swap the questionable FRU with a known-good FRU from the same array.

Figure 8-10I/O Controller Module Flowchart

Chapter 8 Troubleshooting Your Array 8-21

Page 139
Image 139
Dot Hill Systems II 200 FC service manual 4 I/O Controller Module, 10I/O Controller Module Flowchart