Proportional Control Tuning
Appendix A
Proportional Control Tuning
Adjust effective proportional band width
The only adjustment in
Treatment takes too long, but no unacceptable overshoot
After observing treatment performance, some improvement may be possible. If treatment takes too long, and there has been no unacceptable overshoot beyond the setpoint, make one or more the following changes:
∙Increase the reagent delivery capacity.
∙Increase the reagent concentration.
∙Decrease the proportional band width by adjusting the proportional band limit closer to the setpoint.
Unacceptable overshoot
If unacceptable overshoot occurs, make one or more of the following changes:
∙Increase mixing in the treatment tank.
∙Reduce the reagent delivery capacity.
∙Reduce the reagent concentration.
∙Widen the proportional band by adjusting the proportional band limit further from the setpoint.
7/99 | 9782 Series Conductivity/Resistivity Analyzer/Controller - Operator’s Manual Appendix A - 1 |