
Conductivity/Resistivity Analyzer/Controller
10.8Entering Values for Lead Resistance Compensation (Wide Range Only)
Introduction
If you use standard Honeywell cell lead lengths of 7 or 20 feet connected directly to the Analyzer/Controller, no compensation for lead resistance is necessary. Similarly, if a junction box is used to extend the leads up to 150 feet, no compensation is required. However, if longer leads are used (greater than 150 feet), signal quality can be adversely affected unless you enter information that will permit the 9782 to compensate for lead resistance.
If you use a single wire gauge (12, 14, 16, or 18 AWG) in a length up to 1500 feet, simply specify the gauge and length as described in Table
If mixed wired gauges are used, or lead length or wire gauge are not within the stated ranges, the 9782 can still perform the compensation. However, you must first calculate the lead resistance, then put it in terms of the available settings for AWG gauge and length.
The resistance of each available gauge choice (in copper wire) is:
12 AWG = 1.6 ohms per 1000 feet
14 AWG = 2.5 ohms per 1000 feet
16 AWG = 4.0 ohms per 1000 feet
18 AWG = 6.4 ohms per 1000 feet
For example, suppose each lead between the cell and Analyzer/Controller consists of 500 feet of 12 gauge wire and 1000 feet of 18 gauge wire.
9782
1000 ft of 18 AWG
Junction
Box
500 ft. of 12 AWG
Honeywell
Conductivity Cell
Figure 10-1 Example of a Conductivity Loop
Because there are two different types of wire used in each lead to the cell in this example, the total lead resistance is calculated as follows:
(2 x 0.5 x 1.6) + (2 x 1 x 6.4) = 14.4 ohms
Since the 9782 only allows entry of one wire gauge type, we allow for the
14.4 ohms ÷ 6.4 ohms per thousand feet of 18 AWG wire = 2,250 feet
The length to enter is
9782 Series Conductivity/Resistivity Analyzer/Controller - Operator’s Manual | 7/99 |