Softener Monitoring
Softener monitoring by conductivity ratio gives a continuous indication of performance. Sodium is typically more conductive than the hardness minerals it displaces, yielding a higher conductivity at the outlet. A ratio approaching 1 indicates that hardness ions are breaking through and that regeneration is needed.
(Hard) Water Supply
Cell 1
a/n 23192
Cell 2
(Soft) Treated Water
Cell1 |
|
Softening Ratio = Cell2 | Typical Ratio Range is 1 to 1.25 |
Steam Power Measurements
The three conductivity measurements in power plants relate to water chemistry parameters as follows:
∙Specific conductivity
∙Cation conductivity
∙Degassed conductivity
∙Cation minus degassed conductivities
The 9782 Standard Range Analyzer/Controller includes a complete menu of
7/99 | 9782 Series Conductivity/Resistivity Analyzer/Controller - Operator’s Manual Appendix B - 3 |