Two-Cell Applications

Appendix B

Two-Cell Applications

Ion Exchange

Ion exchange operations can achieve especially precise control using the conductivity ratio of two points with each bed. Ratio measurement accounts for feedwater variations when the upstream point is measured at the cation bed inlet. With the upstream point in the bed as shown for following stages, it can identify exhaustion before breakthrough.

Inlet

Cell 2

Cell 1

Cation Bed

Cell 2 Cell 1

Anion Bed

Cell 2

Cell 1

D I Water

Mixed Bed

a/n 23188

Reverse Osmosis

Reverse Osmosis efficiency is monitored by comparing inlet and outlet conductivity (or TDS). Automatic calculations of Percent Rejection or Percent Passage are provided. If readout is in resistivity, cell locations are interchanged. Temperature readout assists with normalized performance comparisons.

 

 

 

 

 

 

C ell 2

 

 

C ell 1

F eed

 

 

 

 

 

 

 

 

 

 

 

 

 

R O Un it

 

 

 

 

 

 

 

 

 

 

 

 

Perm eate

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C on cen trate

 

 

 

 

 

 

 

 

 

 

 

 

a/n 2318 9

 

Cell1

x100

 

 

 

Typical Range is 0 to 20%

Percent Passage = Cell2

 

 

(1

Cell1

)x100

 

Percent Rejection =

 

Typical Range is 80 to 100%

 

 

Cell2

7/99

9782 Series Conductivity/Resistivity Analyzer/Controller - Operator’s Manual Appendix B - 1

Page 139