TROUBLESHOOTING AND REPAIR | |||||||
|
|
|
|
|
| ||
|
|
| RETEST AFTER REPAIR |
|
|
|
|
|
|
|
|
|
| ||
|
| Test | Required Action | Expected Results | |||
|
| Steps |
|
|
|
| |
|
| Lft.display | Rt. display | ||||
|
|
| |||||
|
|
|
|
|
|
| |
46 | This will only appear if a potentiometer is still connect- | dcon | |||||
|
|
| ed to the |
|
|
|
|
|
|
| appears, disconnect the potentiometer from the |
|
|
|
|
|
|
| amphenol connector. |
|
|
|
|
|
|
|
|
|
| ||
47 | Test steps | GAS | On | ||||
|
|
| noid. If an oscilloscope is available, verify that the cur- |
|
|
|
|
|
|
| rent flowing through the gas solenoid is zero before the |
|
|
|
|
|
|
| solenoid is energized, increases to approximately |
|
|
|
|
|
|
| 700mA (pull in current), remains at 700 mA for approxi- |
|
|
|
|
|
|
| mately 150 msec, and decreases to approximately |
|
|
|
|
|
|
| 200mA (hold current). Press the local/remote pushbut- |
|
|
|
|
|
|
| ton to turn the gas solenoid on. |
|
|
|
|
<- 150msec - >
700mA
200mA |
| ||
0mA |
|
|
|
+ |
| ||
|
| Or, the signal can be verified by measuring 12.3 VDC |
|
|
| |
| positive) |
|
|
|
|
48 | Press the local/remote pushbutton again to turn the gas GAS | OFF |
| solenoid off. |
|
After completing all of the above tests, the following will appear on the display.
|
| Verify this message appears for approximately 3 sec- | DIAg | PASS |
|
| onds |
|
|
|
|
|
|
|