Agilent Technologies 6812B, 6834B, 6814B, 6843A OUTPut:RI:MODE, OUTPut TTLTrg SOURce, Outp:Ttlt

Models: 6811B 6813B 6834B 6843A 6814B

1 187
Download 187 pages 38.86 Kb
Page 59
Image 59

Language Dictionary - 3

OUTPut:RI:MODE

This command selects the mode of operation of the Remote Inhibit protection. The following modes can be selected:

LATChing

A TTL low at the RI input latches the output in the protection shutdown state, which can

 

only be cleared by OUTPut:PROTection:CLEar.

LIVE

The output state follows the state of the RI input. A TTL low at the RI input turns the output

 

off; a TTL high turns the output on.

OFF

The instrument ignores the RI input.

 

Command Syntax

OUTPut:RI:MODE <mode>

 

Parameters

LATChing LIVE OFF

 

*RST Value

LATChing

 

Examples

OUTP:RI:MODE LIVE

 

Query Syntax

OUTPut:RI:MODE?

Returned Parameters

<CRD>

Related Commands

OUTP:PROT:CLE

OUTPut:TTLTrg

This command enables or disables the ac source Trigger Out signal, which is available at a BNC connector on the rear of the instrument.

Command Syntax

OUTPut:TTLTrg[:STATe] <bool>

Parameters

0 1 OFF ON

 

*RST Value

OFF

 

Examples

OUTP:TTLT 1

OUTP:TTLT ON

Query Syntax

OUTPut:TTLTrg[:STATe]?

Returned Parameters

0 1

 

Related Commands

OUTP:TTLT:SOUR

 

OUTPut:TTLTrg:SOURce

This command selects the signal source for the Trig Out signal as follows:

BOT

Beginning of transient output

EOT

End of transient output

LIST

Specified by the TTLTrg list

When an event becomes true at the selected TTLTrg source, a pulse is sent to the BNC connector on the rear of the ac source.

Command Syntax

OUTPut:TTLTrg:SOURce <source>

Parameters

BOT EOT LIST

*RST Value

BOT

Examples

OUTP:TTLT:SOUR LIST

Query Syntax

OUTPut:TTLTrg:SOURce?

Returned Parameters

<CRD>

Related Commands

OUTP:TTLT

59

Page 59
Image 59
Agilent Technologies 6812B, 6834B, 6814B, 6843A, 6813B manual OUTPut:RI:MODE, OUTPut TTLTrg SOURce, Outp:Ttlt:Sour List