10.3 Troubleshooting

10. MAINTENANCE

10.3 Troubleshooting

Although magnetic flowmeters rarely require maintenance, failures may occur when the instrument is not operated correctly. This section describes troubleshooting procedures where the cause of the breakdown is identified through receiver indication.

10.3.1 No Indication

START

 

 

 

Is an error being displayed? Check the converter display.

 

Is an error being

YES

Examine in accordance with

 

displayed?

 

Section 6.5: Alarms.

 

NO

 

 

 

Is anything else

NO

 

 

being displayed?

 

 

 

YES

 

Is the fuse blown?

NO

 

 

 

 

 

 

 

YES

 

 

 

Does the

NO

 

 

display return when the fuse

 

 

 

 

 

is replaced?

 

 

 

YES

 

Does the

NO

End

 

 

 

arrow on the tube match the

 

 

 

 

 

flow direction?

 

 

 

YES

 

Perform either of the following:

 

 

a. Reinstall the flowtube in

 

 

 

 

Check whether the flowtube

 

order to make the arrow and

 

 

flow direction match.

 

is filled with fluid.

 

 

 

b. Reverse the setting for the

 

 

 

 

 

 

flow direction.

 

Is the flowtube

NO

 

 

full of fluid?

 

 

 

YES

 

Change the piping or the

 

 

 

 

Check the resistance between

 

mounting condition so that

 

 

the tube fills with the fluid.

 

the flowtube’s A, B, and C

 

 

 

 

 

terminals using a multimeter.

 

 

 

Is the

NO

 

 

resistance 100 M or more

 

 

 

 

 

in each case?

 

 

 

YES

 

 

 

Remove the tube and

 

 

 

inspect the inside of the pipe.

 

 

 

Is foreign

NO

 

 

matter adhering to

 

 

 

the walls?

 

 

 

YES

 

 

 

Remove the foreign matter.

Contact a service center.

 

 

F1005.EPS