6. PARAMETER DESCRIPTION

 

 

 

 

 

 

 

 

 

 

Name

 

Data range

 

Position

Default value

 

 

 

 

 

 

Units

 

 

Item

Display unit

R/W

Display unit

of decimal

Description

 

(*): Indicated item

 

 

 

 

(BRAIN)

 

/BRAIN

 

point

 

 

 

C44

Velocity Check

R

0.000 to 99.999

m/s

3

 

Display of the span setting using

 

 

(VELOCITY CHK)

 

 

 

 

 

flow velocity (m/s).

 

 

 

 

 

 

 

 

 

 

C45

Density Unit

W

kg/m3

 

 

kg/m3

Sets units for density when mass

 

 

(DENSITY UNIT)

 

lb/gal

 

 

 

flow rate is selected.

 

 

 

 

lb/cf

 

 

 

 

 

C46

Mass Flow Density

W

0 to 32000

C45

0 to 4

0

Sets density when mass flow rate

 

 

(MASS DENSITY)

 

 

 

 

 

is selected (with units from C45).

 

C47

User Span Select

W

No

 

 

No

Selects whether or not special

 

 

(USER SPN SEL)

 

Yes

 

 

 

units are used for flow rate units.

 

C48

Flow User Unit

W

8 alphanumeric

 

 

 

Sets the special flow rate units.

 

 

(FL USER UNIT)

 

characters

 

 

 

 

 

C49

Flow User Span

W

0.0001 to 32000

C48

0 to 4

100

Sets span when using special flow

 

 

(FL USER SPAN)

 

 

 

 

 

rate units.

 

 

 

 

 

 

 

 

 

 

C60

R

Good

 

 

 

See “6.5 Alarm Functions”.

 

 

(SELF CHECK)

 

Error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T0604-2.EPS

(4) Item D (Menu D): Total Setting items

Menu D contains setting items such as the totalization scale and the forward/reverse totalized values.

 

Name

 

Data range

 

Position

Default value

 

Item

Display unit

R/W

Display unit

Units

of decimal

Description

(*): Indicated item

 

(BRAIN)

 

/BRAIN

 

point

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D00

Total Set

 

 

 

 

 

 

 

(TOTAL SET)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D10

Total Unit

W

n Unit/P

 

 

Pulse/s (*)

Selects the flow rate unit per one

 

(TOTAL UNIT)

 

u Unit/P

 

 

 

pulse as used for totalization

 

 

 

m Unit/P

 

 

 

display. Linked with B30.

 

 

 

Unit/P

 

 

 

 

 

 

 

k Unit/P

 

 

 

 

 

 

 

M Unit/P

 

 

 

 

 

 

 

Pulse/s

 

 

 

 

 

 

 

 

 

 

 

 

D11

Total Scale

W

0 to 32000

D10

0 to 4

0 (*)

Sets the flow rate per one pulse

 

(TOTAL SCALE)

 

 

(B30)

 

 

for the totalization display.

 

 

 

 

 

 

 

Linked with B31.

D12

Total Decimal Pnt

W

0

 

 

0

Selects position of decimal point

 

(TL DECIMAL)

 

1

 

 

 

for totalization display

 

 

 

2

 

 

 

 

 

 

 

3

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

5

 

 

 

 

 

 

 

6

 

 

 

 

 

 

 

7

 

 

 

 

 

 

 

 

 

 

 

 

D13

Total Low Cut

W

0 to 100

%

0

3 %

Sets the range in vicinity of 0%

 

(TOTAL LOWCUT)

 

 

 

 

 

within which the totalization

 

 

 

 

 

 

 

display will be halted.

 

 

 

 

 

 

 

 

D20

Total Execution

W

Start

 

 

Start

Executes “Start” or “Stop” of the

 

(TOTAL EXEC)

 

Stop

 

 

 

totalization function, or executes

 

 

 

Preset Total

 

 

 

“Preset Total” or “Preset Rev

 

 

 

Preset Rev Total

 

 

 

Total”.

D21

Ttl Set Val Lower

W

0 to 999999

 

0

0

Sets the totalization preset value

 

(TL SET VAL L)

 

 

 

 

 

in the lower 6 digits of the 8-digit

 

 

 

 

 

 

 

totalized value.

 

 

 

 

 

 

 

 

D22

Ttl Set Val Upper

W

0 to 99

 

0

0

Sets the totalization preset value

 

(TL SET VAL U)

 

 

 

 

 

in the upper 2 digits of the 8-digit

 

 

 

 

 

 

 

totalized value.

D23

Ttl Switch Lower

W

0 to 999999

 

0

0

Sets the totalization switch value

 

(TL SWITCH LO)

 

 

 

 

 

in the lower 6 digits of the 8-digit

 

 

 

 

 

 

 

totalized value.

 

 

 

 

 

 

 

 

D24

Ttl Switch Upper

W

0 to 99

 

0

0

Sets the totalization switch value

 

(TL SWITCH UP)

 

 

 

 

 

in the upper 2 digits of the 8-

 

 

 

 

 

 

 

digits totalized value.

 

 

 

 

 

 

 

 

D30

Ttl User Select

W

No

 

 

No

Selects whether or not special

 

(TL USER SEL)

 

Yes

 

 

 

units are used as totalized units.

D31

Ttl User Unit

W

8 alphanumeric

 

 

 

Sets the special totalized units.

 

(TL USER UNIT)

 

characters

 

 

 

 

D60

R

Good

 

 

 

See “6.5 Alarm Functions”.

 

(SELF CHECK)

 

Error

 

 

 

 

T0605.EPS

6-5

IM 01E20C01-01E