6. PARAMETER DESCRIPTION

(8) Item H (Menu H): Display Setting items

Menu H contains setting items that are relevant to display on the display unit.

 

Name

 

Data range

 

Position

Default value

 

Item

 

 

 

Units

Description

Display unit

R/W

Display unit

of decimal

(*): Indicated item

 

(BRAIN)

 

/BRAIN

 

point

 

 

H00

Display Set

 

 

 

 

 

 

 

(DISP SET)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H10

Display Select1

W

Flow Rate(%)

 

 

Flow Rate

Selects content of the first line

 

(DISP SELECT1)

 

Flow Rate

 

 

 

for Display Mode. Linked with

 

 

 

Flow Rate(mA)

 

 

 

B40.

 

 

 

Forward Total

 

 

 

 

 

 

 

Reverse Total

 

 

 

 

 

 

 

Dif Total

 

 

 

 

H11

Display Select2

W

Off

 

 

Off

Selects content of the second line

 

(DISP SELECT2)

 

Flow Rate(%)

 

 

 

for Display Mode. Linked with

 

 

 

Flow Rate

 

 

 

B41.

 

 

 

Flow Rate(mA)

 

 

 

 

 

 

 

Flow Rate(Bar)

 

 

 

 

 

 

 

Forward Total

 

 

 

 

 

 

 

Reverse Total

 

 

 

 

 

 

 

Dif Total

 

 

 

 

 

 

 

Tag No

 

 

 

 

 

 

 

Adhesion Check

 

 

 

 

 

 

 

Communication

 

 

 

 

 

 

 

 

 

 

 

 

H12

Display Select3

W

ame as H11

 

 

Off

Selects content of the third line

 

(DISP SELECT3)

 

(Display Select2)

 

 

 

for Display Mode. Linked with

 

 

 

 

 

 

 

B42.

 

 

 

 

 

 

 

 

H20

Display Cycle

W

200ms

 

 

400ms

Selects the display cycle.

 

(DISP CYCLE)

 

400ms

 

 

 

 

 

 

 

1s

 

 

 

 

 

 

 

2s

 

 

 

 

 

 

 

4s

 

 

 

 

 

 

 

8s

 

 

 

 

H20

Language

W

English

 

 

English

Selects the language used by the

 

(LANGUAGE)

 

Japanese

 

 

 

display unit. Linked with B10.

 

 

 

French

 

 

 

 

 

 

 

German

 

 

 

 

 

 

 

Italian

 

 

 

 

 

 

 

Spanish

 

 

 

 

 

 

 

 

 

 

 

 

H60

R

Good

 

 

 

See “6.5 Alarm Functions”.

 

(SELF CHECK)

 

Error

 

 

 

 

 

 

 

 

 

 

 

 

T0609.EPS

(9) Item J (Menu J): Auxiliary Function Setting items

Menu J contains setting items such as the flow direction, rate limits, and low cut.

 

Name

 

Data range

 

Position

Default value

 

Item

Display unit

R/W

Display unit

Units

of decimal

Description

(*): Indicated item

 

(BRAIN)

 

/BRAIN

 

point

 

 

J00

Aux

 

 

 

 

 

 

 

(AUX)

 

 

 

 

 

 

J10

4-20mA Low Cut

W

0 to 10

%

0

0%

Sets the range in vicinity of 0%

 

(4-20 LOW CUT)

 

 

 

 

 

within which the current output

 

 

 

 

 

 

 

will be 4 mA

 

 

 

 

 

 

 

 

J11

4-20mA Low Lmt

W

-20.0 to 100.0

%

1

-20.0%

Sets the low limit for current

 

(4-20 LOW LMT)

 

 

 

 

 

output

J12

4-20mA High Lmt

W

0.0 to 120.0

%

1

120.0%

Sets the high limit for current

 

(4-20 HI LMT)

 

 

 

 

 

output

J20

Flow Direction

W

Forward

 

 

Forward

Selects the flow direction.

 

(FLOW DIRECT)

 

Reverse

 

 

 

 

J21

Rate Limit

W

0 to10

%

0

5%

Sets the level to reduce output

 

(RATE LIMIT)

 

 

 

 

 

fluctuation.

J22

Dead Time

W

0 to 15

s

0

0s

Sets the dead time to reduce output

 

(DEAD TIME)

 

 

 

 

 

fluctuation. When “0” is set, rate

 

 

 

 

 

 

 

limit function is not available.

 

 

 

 

 

 

 

 

J23

Pulsing Flow

W

No

 

 

No

Selects whether pulsing flow is to

 

(PULSING FLOW)

 

Yes

 

 

 

be supported.

 

 

 

 

 

 

 

 

J24

T/P Damp Select

W

Damping

 

 

Damping

Selects whether the flow rate value

 

(T/P DAMP SEL)

 

No Damping

 

 

 

obtained through damping calculation

 

 

 

 

 

for total/pulse or the instantaneous

 

 

 

 

 

 

 

 

 

 

 

 

 

 

flow rate value (no damping) for

 

 

 

 

 

 

 

total/pulse is to be used.

 

 

 

 

 

 

 

T0610-1.EPS

6-9

IM 01E20C01-01E