4.4.7Connecting to External Instru- ments

In case of explosion proof type for CENELEC ATEX, FM, and CSA certification, connect wiring as shown in the figure below.

In case of the explosion proof type, the protective

grounding 4 to 20 mA DC Current Output of remote flowtube must be connected to a suitable IS grounding system. In that case, Manual background

(functional grounding terminal) need not be connected.

I+

I–

SO1+ SO2+ COM

AL+ AL–

C

SA

A

B

SB

CURRENT OUT

STATUS OUT

ALARM OUT

 

 

SIGNAL

 

 

 

 

 

 

 

 

 

 

AXFA11 Converter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

N/–

L/+

 

 

 

 

 

 

 

P+

P–

SI1+

SI2+

COM

 

 

 

 

 

 

POWER SUPPLY

 

 

 

 

 

 

 

 

PULSE OUT

 

STATUS IN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AXFC Dedicated signal

 

 

cable

 

 

Excitation cable

 

 

 

 

Converter

Remote

 

 

flowtube

 

 

 

 

 

SA

Taping*

 

 

A

A

 

 

B

B

 

 

SB

Taping*

A

 

C

C

 

EX1

EX1

B

EX2

EX2

EX2

* Individually tape and insulate the

 

 

 

 

shields corresponding to SA and

 

EX1

SB on the remote flowtube side.

 

 

 

 

C

 

 

 

Remote flowtube

 

F0416.EPS

Figure 4.4.6 Wiring Diagram

(3)Connection with the Remote Flowtube (General-Purpose Use, Submersible Type, Size 500 to 1000 mm (20 to 40 in.))

Connect wiring as shown in the figure below.

I+

I–

SO1+ SO2+ COM

AL+ AL–

C

SA

A

B

SB

CURRENT OUT

STATUS OUT

ALARM OUT

 

 

SIGNAL

 

 

4-20mA out

 

 

 

 

 

 

AXFA11 converter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

N/–

L/+

 

 

P+

P–

SI1+

SI2+

COM

 

 

 

 

POWER SUPPLY

 

 

 

PULSE OUT

 

STATUS IN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Shortbar

 

 

AXFC dedicated

 

Excitation

signal cable

 

 

Remote

 

cable

Converter

 

flowtube

 

 

 

 

 

SA

Taping*

 

 

A

A

 

 

B

B

 

 

SB

Taping*

A

EX2

C

C

EX1

EX1

 

B

 

EX2

EX2

 

* Individually tape and insulate

 

 

 

 

the shields corresponding to SA

 

EX1

and SB on the remote flowtube

 

C

side.

 

 

 

 

 

Remote flowtube

 

F040217.EPS

Figure 4.4.7 Wiring Diagram

4. WIRING

(4)Connection with the Remote Flowtube (General-Purpose Use, Submersible Type, Size 1100 to 2600 mm (44 to 104 in.))

Connect wiring as shown in the figure below.

I+

I–

SO1+ SO2+ COM

AL+ AL–

C

SA

A

B

SB

CURRENT OUT

STATUS OUT

ALARM OUT

 

 

SIGNAL

 

 

4-20mA out

 

 

 

 

 

 

AXFA11 converter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

N/–

L/+

 

 

P+

P–

SI1+

SI2+

COM

 

 

 

 

POWER SUPPLY

 

 

 

PULSE OUT

 

STATUS IN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Shortbar

 

 

AXFC dedicated

 

 

signal cable

 

 

Excitation

 

 

 

cable

Converter

Remote

 

 

 

 

flowtube

 

 

 

 

 

SA

Taping*

 

 

A

A

 

 

B

B

A

EX2

SB

Taping*

C

C

 

B

 

EX1

EX1

 

EX2

EX2

 

 

 

 

* Individually tape and insulate

 

EX1

the shields corresponding to SA

 

and SB on the remote flowtube

 

C

side.

 

 

Remote flowtube

 

F040218.EPS

Figure 4.4.8 Wiring Diagram

4.4.7Connecting to External Instru- ments

WARNING

Before wiring with external instrument, be sure to turn off the power supply for AXFA11 converter and any external instruments.

Connect the AXFA11 terminal to external instruments, giving attention to the following points.

4 to 20 mA DC Current Output

AXFA11

l+

Receiver

l-Instrument

Resistive Load Max. 1 k.

(When using BRAIN/ HART communication, more than 250 , less than 600 ).

F0417.EPS

Figure 4.4.9 4 to 20 mA DC Output Connection

4-7

IM 01E20C01-01E