APC AXFA11G G10 Low Alarm = -110% G11 High Alarm = 80% G12 Low Low Alarm = -110%, Output Example

Models: AXFA11G

1 118
Download 118 pages 18.28 Kb
Page 55
Image 55
G10: Low Alarm = -110%

Output Example 3

The high alarm (H) is set to 80% or more of the flow rate span; the high-high alarm (HH), to 90% or more.

Settings are:

G10: Low Alarm = -110%

G11: High Alarm = 80%

G12: Low Low Alarm = -110%

G13: High High Alarm = 90%

[%]

High High Alarm

100

 

90

 

80

 

 

High Alarm

 

Instantaneous flow rate

50

 

0

Time (t)

SO1

H

 

 

 

 

 

 

L Alarm set to

 

 

 

 

 

-110% indicates

 

 

 

 

 

that the alarm is

SO2

 

HH

 

 

disabled.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LL Alarm set to -110% indicates

 

 

 

 

that the alarm is disabled.

 

 

 

 

 

 

 

AL

HH

Select “H/L Alarm” forF10: SO1 Function

Select “HH/LL Alarm” forF11: SO2 Function

Select “Closed (On) Act” forF14: SO1/2 Active Mode

Select “Open (Off) Act” forG20: Alm Out Act Mode

Select “Yes” forG33: Alm-HH/LL

F0612.EPS

NOTE

Although the same items can be selected using the SO1 output terminal (selected for F10) and the SO2 output terminal (selected for F11), output is identical for both.

Setting values of -110% and 110% are used to disable corresponding functions; and accord- ingly, status output can be customized for specific purposes.

6. PARAMETER DESCRIPTION

[G14: H/L Alarm Hys] Setting of upper/lower alarm value hysteresis width

This parameter sets the hysteresis width for upper and lower alarm value, using a % value of the maximum span.

Output Example

The hysteresis width is set to 5%.

Settings are:

G10: Low Alarm = 30%

G11: High Alarm = 80%

G12: Low Low Alarm = 20%

G13: High High Alarm = 90%

G14: H/L Alarm Hys = 5%

[%]

 

 

 

High High Alarm

100

 

 

 

 

 

 

 

90

 

85%

 

 

80

 

 

 

 

75%

 

 

 

 

 

High Alarm

 

 

 

 

 

 

 

Instantaneous flow rate

50

 

 

 

 

 

 

 

 

35% Low Alarm

30

 

 

 

25%

20

 

 

 

 

 

 

 

 

 

 

 

Low Low Alarm

0

 

75%

 

Time (t)

 

H

L

35%

SO1

 

 

 

 

 

 

 

HH

85%

LL

25%

SO2

 

 

 

 

 

 

AL

HH

 

LL

 

 

85%

25%

 

 

 

Select “H/L Alarm” forF10: SO1 Function

Select “HH/LL Alarm” forF11: SO2 Function

Select “Closed (On) Act” forF14: SO1/2 Active Mode

Select “Open (Off) Act” forG20: Alm Out Act Mode

Select “Yes” forG33: Alm-HH/LL

F0613.EPS

[G20: Alm Out Act Mode] Setting of the active mode for the alarm output.

This parameter selects the active mode for the alarm output terminal.

Setting

Function

 

 

Closed (On) Act

When an alarm occurs, alarm output

becomes "Closed (On)."

 

 

 

Open (Off) Act

When an alarm occurs, alarm output

becomes "Open (Off)."

 

 

 

T0631.EPS

6-27

IM 01E20C01-01E

Page 55
Image 55
APC AXFA11G user manual G10 Low Alarm = -110% G11 High Alarm = 80% G12 Low Low Alarm = -110%, Output Example